Time Period Charge And Discharge Mode; Meter Instruction; Function Description - Alpha ESS STORION-T50 Operation & Maintenance Manual

Hide thumbs Also See for STORION-T50:
Table of Contents

Advertisement

EMS OPERATION

5.2.4. Time Period Charge and Discharge Mode

A.Turn on the function of force charge:EMS->Setting-> Function->System Mode->
Force Charge->Enable;
B. Set up the first charge start time: EMS->Setting-> Function->System Mode-> Charge
Start Time 1;
C. Set up the first charge end time: EMS->Setting-> Function->System Mode-> Charge
End Time 1;
D. Set up the second charge start time: EMS->Setting-> Function->System Mode->
Charge Start Time 2;
E. Set up the second charge end time: EMS->Setting-> Function->System Mode-> Charge
End Time 2;
F. Set up the charge cut SOC of the system: EMS->Setting-> Function->System Mode->
Charge Cut SOC;
G. Turn on the function of allow discharge:EMS->Setting-> Function->System Mode->
Allow Discharge->Enable;
H. Set up the first discharge start time: EMS->Setting-> Function->System Mode->
Discharge Start Time 1;
I. Set up the first discharge end time: EMS->Setting-> Function->System Mode->
Discharge End Time 1;
J. Set up the second discharge start time: EMS->Setting-> Function->System Mode->
Discharge Start Time 2;
K. Set up the second discharge end time: EMS->Setting-> Function->System Mode->
Discharge End Time 2;
L. Set up the discharge cut SOC of the system: EMS->Setting-> Function->System
Mode-> DischargeCutSOC->11%;
20
21
06

Meter Instruction

6.1 Function Description

Figure 6-1 Schematic diagram of the appearance of the meter
Object
A
B
C
D
E
F
SET
Table 3 Function Description
Name
Description
Display Screen
Data display and setting display
SET
Men u button: Enter / Exit menu.
Up button: View the voltage and current in the
viewing interface, move left in the programming
interface and modify the flashing shift.
Down button:View the power in the viewing
interface, move right in the programming
interface and modify the flashing shift.
Enter button:Check the power in the viewing
interface and save the settings in the program-
ming interface.
Connect to EMS or other meters through
network cable to realize communication between
Plug
devices.
METER INSTRUCTION