Unpacking; Installing The Commander Ii And Ii+ System; Figure 7: Ac Earth Termination; Figure 7A: External Earth Termination - NewMar Commander II Series Manual

Table of Contents

Advertisement

Recommended rack size is 19" and minimum 600mm deep.
6.3

Unpacking

Upon unpacking, check that the unit is not damaged, and that you have the required number of modules and
blank panels (if and as appropriate for your system).
N
: Do not fit rectifier modules until the Commander power system has been installed into the rack.
OTE
6.4 Installing the Commander System
STEP 1: Remove the Drip cover from the
system by removing the 3 thumbscrews.
Retain for reuse.
STEP 2: Mount the system in the cabinet or
rack as appropriate.
STEP 2: Connect the AC supply.
Terminate the cables to the input circuit breakers and
the terminal blocks for Earth and phase to phase (or L1
to L2) (see AC wiring options for Commander II series).
N
: the AC terminals accept up to 1/0 AWG/55mm
OTE
cables.
N
: the AC earth terminal is connected directly to the
OTE
system chassis.
N
: AC and DC EARTHING - This system has a built-
OTE
in AC to DC earth connection. No extra AC to DC earth
link cable is required. However, an additional
grounding point has been provided to ensure the unit
meets any additional requirements. Removing this link
will void the warranty. Please check with NewMar
should this link be required to be removed.
STEP 4: Connect the Load.

Figure 7: AC Earth Termination

NewMar Power System Manual
Model: COMMANDER II AND COMMANDER II+
AC
Chassis Earth
Figure 5 Top Cover
2
Figure 6: AC Termination

Figure 7A: External Earth Termination

M-CMDRII 063022