Additional Features; Physical Dimensions And Weight; Energy Manager; Em4X-01 Interface - NewMar Commander II Series Manual

Table of Contents

Advertisement

Battery Low Voltage Disconnect 500A rating
CTO Configuration:
AC input MCB with surge protection device, type 2
4 x DIN style 27mm battery MCBs
18 x DIN style 18mm load MCBs (max 12 when fitted with 4 battery breakers)
Low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD)
5.1.2 Current Capacities
Commander II system capacity is up to 720A with a maximum of 12x RM3048HE power modules. The
Commander II+ system capacity is up to 480A with a maximum of 8x RM3048HE and a maximum of 8
DC-DC converters with 12V or 24V output at 40A and 43A, respectively.

5.1.3 Additional Features

AC input MCB with surge protection device, type 2
I/O board
AC monitoring including voltage, frequency and current
Fan control
Battery control monitoring
Battery fuse fail
Site monitoring
5.1.4 Physical Dimensions and Weights
Table 1: Commander II & II+ dimensions and weights
Model
Depth (Total)
Width (Total)
Height
Weight without rectifiers
Weight with max.
rectifiers
5.2

Energy Manager

5.2.1 EM4x-01 Interface

Status LEDs
NewMar Power System Manual
Model: COMMANDER II AND COMMANDER II+
Commander II
380mm
483mm (19"
mount)
267mm (6U)
22.7kg
38.3kg
Micro-USB

Figure 2: EM4x-01 Front Panel Interface

Commander II+
380mm
483mm (19"
mount)
311mm 7U
22.7kg
46.7kg
Touchscreen
M-CMDRII 063022
Page 8 of 43
Version 1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Commander ii

Table of Contents