Figure
12: Controller Layout

6.5 Rectifier Module Insertion and Removal

Figure 13: RM3048HE Front Panel
plugged in to the system prior to power-up.
The rectifier modules are designed for "hot plug-and-play". It is safe to insert and remove modules at any
time, even when the system is loaded.
The rectifier modules are self-addressing, meaning that no setup
is required for the EM4x controller to determine rectifier
addressing.
IMPORTANT:
if a rectifier is removed from the system and then
plugged into another rectifier slot, you must wait for the red LED
to extinguish (this clears the address setting in the EPROM).
When inserting the module, ensure that it is pressed hard into
the system. The locking button should click. See
To remove the module, press the locking button while pulling on
the "handle" that is integrated into the front panel. See
Check that any blank rectifier slots have the rectifier blank panel
inserted to prevent air back-flow.
NewMar Power System Manual
Model: COMMANDER II AND COMMANDER II+
Integrated Handle
Locking Button
Rectifier modules are shipped separately. They must be
Figure 14: Inserting a Rectifier
Figure 14.
Pull out the rectifier
Figure
15.
Figure 15: Removing a Rectifier
Press the locking button
M-CMDRII 063022