Commander II Series AC Input Wiring Options
Note: AC wiring should only be performed by qualified electrician or technician
familiar with AC wiring practices and local electrical code.
Option 1:
208 VAC three Phase w/ three 2 pole circuit breakers
Neutral
Ground
L1
L2
L1
L2
L3
Neutral
Ground
Option 2:
208 VAC Three Phase w/ two 3 pole circuit breakers
Neutral
Ground
L1
L2
L3
L1
L2
L3
Neutral
Ground
Technical Service: 800-241-3897 • E-mail: techservice@newmarpower.com
Not Used
Not Used
Not Used
Not Used
70 Amp Three Pole
Circuit Breaker
Newmar • 1580 Sunflower Ave, Suite 100, Costa Mesa, CA 92626
70 Amp Two Pole
70 Amp Two Pole
70 Amp Two Pole
L2
Commander II AC Terminal
Block. 2 AWG Max Wire Size
60 Amp Three
Pole Circuit
Breaker
L2
Commander II AC Terminal
Block. 2 AWG Max Wire Size
L2
L2
L1
L1
Commander II PE Terminal
Block. 2 AWG Max Wire Size
maintain proper AC phasing
A-L2
C-1
L2
L1
Commander II PE Terminal
Block. 2 AWG Max Wire Size
L1 TO C-L2
L2 TO C-L1
L1 TO B-L2
L2 TO A-L1
L1
Verify Correct wiring to
maintain proper AC phasing
L1 TO C-L2
L2 TO B-L2
L3 TO A-L2
Verify Correct wiring to
L1 TO A-L1
L2 TO C-L1
L3 TO B-L1
L1
PE