NewMar SPS 12-20 Installation & Operation Manual

NewMar SPS 12-20 Installation & Operation Manual

Site power system

Advertisement

Quick Links

Installation/Operation Manual
Models: SPS 12-20, SPS 24-10, SPS 48-6

Table of Contents

P.O. Box 1306
Newport Beach
California 92663
Site Power System
Page Table of Contents
2
2
2
2
2
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
6
7
4.9
E-Mail: techservice@newmarpower.com
Page
7
7
8
8
9
9
9
9
10
10
10
11
11
11
12
12
12
12
12
13
13
13
14
Manual-SPS
As of May 2012
Phone: 714-751-0488
Fax: 714-957-1621

Advertisement

Table of Contents
loading

Summary of Contents for NewMar SPS 12-20

  • Page 1: Table Of Contents

    Site Power System Installation/Operation Manual Models: SPS 12-20, SPS 24-10, SPS 48-6 Table of Contents Page Table of Contents Page 1 Principles of Operation 2.5 Multiple Units 1.1 Introduction 2.6 Internal Alarm Card 1.2 LEDs 2.6.1 Relays 1.3 Display 2.6.2 Rectifier Fail/AC Fail 1.4 Auto Float Boost...
  • Page 2: Principles Of Operation

    Voltage Maximum Power Model Volts Current Range Voltage Voltage Range Current Rating SPS 12-20 14.5V 11.5 - 15V 300W 85 - 275 4A @ 110V SPS 24-10 45 - 100 Hz. 22 - 30V 300W VAC* 2A @ 220V SPS 48-6...
  • Page 3: Low Voltage Disconnect And Reset

    The LVD voltage and the LVD Hysterisis voltage are preset in the factory, but may be adjusted to suit the specific battery installation - see Section 4.7. Model Voltage Adjustment Maximum Load Current SPS 12-20 9.5 to 12V SPS 24-10 19 to 24V SPS 48-6 38 to 38V Do not exceed the maximum load current, as the LVD circuitry may be damaged.
  • Page 4: Output Over Voltage Shut Down

    Output Over Voltage Shut Down The SPS will automatically shutdown if the output voltage exceeds the preset value. The Over Voltage Shutdown voltage is preset in the factory but may be adjusted. Input Over Voltage Shut Down If the input voltage is outside the specified range, the SPS may shut down until the allowed voltage is restored. 1.10 Input Inrush Current Limiter On startup, the peak AC inrush current is limited to twice the maximum operating current.
  • Page 5: Internal Alarm Card

    • Low voltage output When SPSs are connected in parallel using an RJ45 patch cable (Newmar part # 466-4524-0) to connect between the alarm and control interface on each rectifier, the alarm outputs on the Alarm Card give the status of all the connected units.
  • Page 6: Cabling

    Caution: The rectifier must be mounted on a vertical surface so that it stands vertically, and is not laid flat on its side. Observe orientation arrow printed on front panel. Do not mount rectifiers above each other. Cabling It is important that all cables (except AC) are less than 10 feet in length. The rectifier is not designed for cables greater than 10 feet or for connection to outside cables.
  • Page 7: Temperature Compensation

    If the LVD functionality is not required, the load must still be connected to the Load connection (not directly onto the battery). It is recommended that two wires are run in parallel for both the +v and –v Battery and Load connections. 14 AWG wire should be used for the connectors.
  • Page 8: Relays

    When units are connected in parallel using an RJ45 cable to connect between the alarm and control interface, the alarm outputs on the Alarm Card give the status of all the connected units. This means that you only need one alarm card connected to the external alarm circuitry when the units are connected in parallel. The diagram on the following page describes the alarm contacts found on the right side of the unit.
  • Page 9: Rectifiers In Parallel

    The internal alarm cards of multiple parallel units can be connected in parallel (using RJ45 Cat. 5 style patch cord, Newmar part # 466-2524-0, 24” length) so that the alarm condition can be reported if any alarm is triggered in any SPS.
  • Page 10: Troubleshooting

    However for IEC 60950 the fuse ratings are required to be specified. The following fuses are soldered to the PCB: • FH101 – 125mA 250V ETF Bussmann Model FH1, FH2 FH200, FH401 FH201, FH402 SPS 12-20 5A 250V ceramic slow blow 40A 32V Blade SPS 24-10 5A 250V ceramic slow blow 40A 32V Blade...
  • Page 11: 4.1 Standard Settings

    The SPS must be disconnected from the battery and load. The adjustment trimpots are accessible on the rear side of the rectifier, with the AC input oriented to the left, the trimpots read as follows. 4.1 Standard Settings Item SPS 12-20 SPS 24-10 SPS 48-6 Boost Voltage 14.2V...
  • Page 12: Adjust Boost To Float Current Threshold

    Adjust Boost to Float Current Threshold Connect a variable load (set to minimum load) to the battery connections of the SPS. Disconnect the Temperature Compensation Probe. Connect an accurate current meter in series with the load. Turn on AC to the unit, wait 10 seconds and then adjust the load up slowly until the unit goes into Boost Charge mode (as indicated on the LEDs).
  • Page 13: Adjusting The Alarm Output Volt Low/High Setting

    Warranty and Factory Contact Information Newmar warrants that Site Power System be free from defects in material and workmanship for two years from date of purchase. If a problem with your SPS, or if you have any questions about the installation and proper operation of the unit, please contact NEWMAR’s Technical Services Department:...
  • Page 14: Dimensional Drawings

    Dimensional Drawings P.O. Box 1306 Phone: 714-751-0488 Newport Beach Fax: 714-957-1621 California 92663 E-Mail: techservice@newmarpower.com...

This manual is also suitable for:

Sps 24-10Sps 48-6

Table of Contents