Set Batter Current Limit - NewMar Commander II Series Manual

Table of Contents

Advertisement

EM4x Web UI page: Charge
Example:
Site Settings:
N
:
OTE
Both the 10 hour and secondary battery capacity hour rates should be set at the
same time. The EM4x compares rates to ensure the battery data is accurate and may
not accept the setting if an inaccuracy is detected.
11.1.5 Set Battery Current Limit
Consult battery manufacturer's data for maximum battery recharge current settings.
The Battery Current Limit is set as a percentage of the 10-hour rate entered above.
It is recommended this value is set at the highest rate allowable to ensure the battery is recharged as fast as
possible.
In some systems, especially larger systems, this may require limiting further because of the number of rectifiers
available, rather than the maximum setting.
EM4x Web UI page: Battery>Battery Settings
Enable Battery Current Limit by clicking on the tick icon beside the field.
Example:
Site Settings:
NewMar Power System Manual
Model: COMMANDER II AND COMMANDER II+
Done 
Done 
M-CMDRII 063022
Page 25 of 43
Version 1.0