Appendix V
Enabling the Ambient Temperature Sensor
To enable the Ambient Temperature Sensor
Physically connect the ambient temperature sensor (purchased separately) to T2 on the EM4x controller IO board
Login to the controller via the web GUI
Navigate to the Input Logic page, after the last entry press the
From the 1
drop down menu, select Measurement and Controls > Input > Ambient Temperature
st
From the 2
drop down menu, select Measurement and Controls > IO Board > IO Board 1 Temperature 2
nd
Press the Save button to implement changes
Navigate to the Alarm Configuration > Alarm Configuration > General Alarms
Expand the General Alarms by selecting the +
Enable the Ambient Temperature Faulty, Ambient Temperature High, and Ambient Temperature Low alarms
Press the Save button to implement changes
This addition can be accomplished with power to the system enabled. Exercise extreme caution when working with
energized equipment. It may be necessary to refresh the browser after completion.
This addition can be accomplished without power to the system by utilizing the USB connection on the front of the controller.
Upon completion of the programming, the ambient temperature sensor will show a fault. This is normal as the IO board does
not receive power when programmed from the USB without power enabled.
Technical Service: 800-241-3897 • E-mail: techservice@newmarpower.com