Ventilation

The performance of the rectifier or other power modules can be limited if the ventilation is restricted. The
rectifier is cooled by drawing air into the front of the unit with a single fan. This air passes through the rectifier
cooling the electronics and exiting the rectifier at the rear. For efficient airflow:
Check the air at the front of the rack is at ambient temperature and not being heated by other
equipment.
That the rectifier shelf has at least 3"/75mm clear horizontal space behind it. This space must be clear
of cables and any other components that may restrict air movement.
N
: if multiple rectifier shelves are installed then there should be at least 3"/75mm clear horizontal
OTE
space per shelf.
Check the free space in the rack continues vertically to the exhaust point at the top of the rack,
without impediment.
Check the hot exhaust air does not re-circulate to the front of the rack as this will be drawn into the
rectifiers again, in effect raising the apparent ambient temperature.
Check the operating environment is low dust and fiber.
Pay particular attention to the quality of rectifier air intake. Insects, sand, and other
extraneous matter ingress seriously impacts the performance of the rectifiers.
7
E
M
NERGY
ANAGER
The energy manager is configured via a web browser-based user interface (Web UI).
There are two methods to access the Web UI:
1. Ethernet connection from the J305 ethernet connector
2. Front panel micro-USB local connection
7.1

Access Levels

There are 3 access levels for the Energy Manager Web UI:
enaguest
enabasic
enaadvanced
The default password for all levels = ena123
7.2

Ethernet Port Connection

careful handling and proper precautions to be taken – an electrostatic discharge
protection device must be worn.
Figure 16: Energy Manager Ethernet Port
NewMar Power System Manual
Model: COMMANDER II AND COMMANDER II+
C
ONNECTIVITY AND THE
: can only view status of system
: reduced privilege, can view settings and system status
: this user has normal full control access of the system
The energy manager contains static sensitive components that require
W
UI
EB
M-CMDRII 063022
Page 17 of 43
Version 1.0