Mitsubishi Electric FR-C500 Instruction Manual page 99

Transistorized inverter
Table of Contents

Advertisement

Computer Link Operation Setting
No.
Item
Link
parameter
11
expansion
setting
REMARKS
For the instruction code HFF, its set value is held once it is written, but changed to 0 when the
inverter is reset or all clear is performed.
<Error Code List>
The corresponding error code in the following list is displayed if an error is detected in
any communication request data from the computer.
Error
Item
Code
Computer NAK
H0
error
H1
Parity error
Sum check
H2
error
H3
Protocol error
H4
Framing error
H5
Overrun error
H6
———
H7
Character error
H8
———
H9
———
HA Mode error
Instruction code
HB
error
Data range
HC
error
Instruc
tion
Code
H00 to H6C and H80 to HEC parameter values are
changed.
H7F
H00: Pr. 0 to Pr. 99 values are accessible.
H01: Pr. 145 value is accessible.
H03: Pr. 331 to Pr. 342 values are accessible.
HFF
H05: Pr. 503 to Pr. 533 values are accessible.
H09: Pr. 990 to Pr. 993 values are accessible.
The number of errors consecutively detected in
communication request data from the
computer is greater than allowed number of
retries.
The parity check result does not match the
specified parity.
The sum check code in the computer does not
match that of the data received by the inverter.
Data received by the inverter is in wrong
protocol, data receive is not completed within
given time, or CR and LF are not as set in the
parameter.
The stop bit length is not as specified by
initialization.
New data has been sent by the computer
before the inverter completes receiving the
preceding data.
The character received is invalid (other than 0
to 9, A to F, control code).
Parameter write was attempted in other than
the computer link operation mode or during
inverter operation.
The specified command does not exist.
Invalid data has been specified for parameter
write, frequency setting, etc.
Description
Definition
———
———
———
90
Number
of Data
Digits
2 digits
Inverter Operation
Brought to an alarm
stop (PUE) if error
occurs continuously
more than the
allowable number of
retries.
———
Does not accept
received data but is not
brought to alarm stop.
———
———
Does not accept
received data but is not
brought to alarm stop.

Advertisement

Table of Contents
loading