Run Key Rotation Direction Selection (Pr. 17); Stall Prevention Function And Current Limit Function (Pr. 21, Pr. 22) - Mitsubishi Electric FR-C500 Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

3.3.9
key rotation direction selection (Pr. 17)
RUN
Used to choose the direction of rotation by operating the
operation panel.
Parame
ter
17
RUN key rotation direction selection
3.3.10 Stall prevention function and current limit function
(Pr. 21, Pr. 22)
You can make setting to disable stall prevention caused by overcurrent and to
prevent the inverter from resulting in an overcurrent trip if an excessive current
occurs due to sudden load variation or ON-OFF, etc. in the output side of the
running inverter.
• Stall prevention
If the current exceeds the limit value, the output frequency of the inverter is
automatically varied to reduce the current.
• Fast-response current limit
If the current exceeds the limit value, the output of the inverter is shut off to
prevent an overcurrent.
Parame
ter
21
Stall prevention function selection
Stall
Prevention
Operation
Fast-
Selection
#
Response
Current
Activated
! ! ! !
Limit
Pr. 21
#
:
Setting
activated
Activated
! ! ! !
: Not
activated
#
# # #
0
!
# # #
1
#
2
!
3
#
# ! #
4
!
# ! #
5
#
6
!
7
Name
Name
OL Signal
Output
#
:
:
Operation
continued
: Not
! ! ! !
:
Operation
not
continued
(*)
#
#
! # #
#
! # #
#
#
#
! ! #
#
! ! #
#
Factory
Setting
Setting
Range
0
0, 1
Factory
Setting
Setting
Range
0
0 to 31, 100
Fast-
Response
Current
Limit
Pr. 21
#
:
Setting
Activated
! ! ! !
: Not
activated
!
9
#
10
!
11
#
12
!
13
#
14
!
15
#
16
63
Basic Functions
key of the
RUN
Remarks
0: Forward rotation
1: Reverse rotation
Stall
Prevention
Operation
OL Signal
Selection
Output
#
#
:
:
Activated
Operation
! ! ! !
continued
: Not
! ! ! !
:
activated
Operation
not
continued
(*)
# # !
#
! # !
#
! # !
#
# ! !
#
# ! !
#
! ! !
#
! ! !
#
# # #
!
3