OPTIWAVE-M 7400 C
Screen
02/2019 - MA OPTIWAVE-M 7400 C R01 en
Steps
[ ] or [ ] for the selection of the
tank type (Storage, Stilling Well,
Agitator or Process).
[^] to confirm.
[>] to change the position of the
cursor.
[ ] to decrease the value (or move
the decimal point one digit to the left)
or [ ] to increase the value (or move
the decimal point one digit to the
right).
[^] to confirm.
[ ] or [ ] for the selection of the
measurement name (Distance,
Level, Sensor Value or Reflection,
Volume (Mass), Ullage Volume
(Ullage Volume).
[^] to confirm.
[>] to change the position of the
cursor.
[ ] to decrease the value (or move the
decimal point one digit to the
left) or [ ] to increase the value (or
move the decimal point one digit to
the right).
[^] to confirm.
www.krohne.com
OPERATION
Description
Tank type. Make a selection from the list of
parameters. If the surface of the product is flat,
select "Storage". If the surface of the product is
disturbed, select "Process". If the surface of the
product is agitated with vortexes and foam,
select "Agitator". If the device is installed in a
stilling well, select "Stilling Well".
If you set A4.1.2.1 Tank Type to "Stilling Well",
there are two more steps after menu item
A4.1.2.2 Tank Height (the subsequent step):
A4.1.2.3 Stilling Well Height and A4.1.2.4 Stilling
Well Diameter.
Tank height. The distance from the flange
face / thread stop of the tank connection
down to the tank bottom. If the tank has a
dish-shaped or conical bottom, the tank
height is measured to a point on the tank
bottom directly below the antenna.
Current output 1 variable. The manufacturer sets
the current output variable (for current output
1) to "Distance" before delivery.
If it is necessary to measure volume, ullage
volume, mass or ullage mass.
0% range. Use this step to give the 0% output
setting in the tank.
Refer to the illustrations that follow. When
menu item A4.1.3.1 Current Out. 1 Var. is set to
"Level", illustration 1 shows the position of 0%
output as a level above the tank bottom. When
menu item A4.1.3.1 Current Out. 1 Var. is set
to "Distance", illustration 2 shows the position
of 0% output as a distance below the flange
facing or thread stop of the process
connection.