KROHNE OPTIWAVE-M 7400 C Short Manual page 42

24 ghz radar (fmcw) level transmitter foragitated and corrosive liquids
Table of Contents

Advertisement

OPERATION
4
Menu
Function
No.
B1.1.8
Distance Lin.
B1.1.9
Ullage Volume
B1.1.10
Ullage Mass
B1.2 Output
42
Function description
This sets the device to a given test
distance value (linearized). This menu
item is only available if you set up a
linearization table in menu item C3.1 Edit
Table. Make sure that menu item C4.1.1
Current Out. 1 Var. is set to "Lin. Distance"
before the device simulates a linearized
distance value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [^] to confirm the value,
the display shows the question "Start
Simulation?" Push [ ] or [ ] to set the
display to "Yes". Push [^] again to start
the test. The device goes to back to
Normal mode after 1 hour.
Minimum access level to do the
procedure: Expert
This sets the device to a given test ullage
volume value. This menu item is only
available if you set up a conversion
(volume) table in menu item C3.1 Edit
Table. Make sure that menu item C4.1.1
Current Out. 1 Var. is set to "Ullage
Volume" before the device simulates an
ullage volume value. This procedure sends
an output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [^], the display shows
the question "Start Simulation?" Push
[ ] or [ ] to set the display to "Yes".
Push [^] again to start the test. The
device goes to back to Normal mode
after 1 hour.
Minimum access level to do the
procedure: Expert
This sets the device to a given test ullage
mass value. This menu item is only
available if you set up a conversion (mass)
table in menu item C3.1 Edit Table. Make
sure that menu item C4.1.1 Current Out. 1
Var. is set to "Ullage Mass" before the
device simulates a mass value. This
procedure sends an output signal that
agrees with the test reading. Output will
change to the selected value,
independent of the measurement data.
When you push [^] to confirm the value,
the display shows the question "Start
Simulation?" Push [ ] or [ ] to set the
display to "Yes". Push [^] again to start
the test. The device goes to back to
Normal mode after 1 hour.
Minimum access level to do the
procedure: Expert
www.krohne.com
Selection list
min-max:
-5000.0...+5000.0 m /
+03
+03
-196.85
...+196.85
in /
-16404...+16404 ft
min-max:
0
+06
.... 1.00
min-max:
0
+09
.... 10.000
kg
02/2019 - MA OPTIWAVE-M 7400 C R01 en
OPTIWAVE-M 7400 C
Marine
Default
1
1
1