KROHNE OPTIWAVE-M 7400 C Short Manual page 45

24 ghz radar (fmcw) level transmitter foragitated and corrosive liquids
Table of Contents

Advertisement

OPTIWAVE-M 7400 C
C – Full Setup menu
Menu
Function
No.
C1 Install. Parameters
C1.1
Tank Type
C1.2
Tank Height
C1.3
Stilling Well
Height
C1.4
Stilling Well
Diameter
C1.5
Blocking
Distance
C1.6
Time Constant
02/2019 - MA OPTIWAVE-M 7400 C R01 en
Function description
The conditions in which the device is used. If the
surface of the product is flat, select "Storage". If
the surface of the product is disturbed, select
"Process". If the surface of the product is
agitated with vortexes and foam, select
"Agitator". If the device is installed in a stilling
well, select "Stilling Well".
Minimum access level to change the
setting: Expert
Tank height is the distance from the flange
face/thread stop of the process connection to
the tank bottom. If you use the device for an
LPR (open-air) application, this value is the
maximum distance that the device must
measure (the measuring range).
Minimum access level to change the
setting: Expert
The height of the stilling well. This menu item is
available if you set "Stilling Well" in menu item
C.1.1 Tank Type.
Minimum access level to change the
setting: Expert
The inner diameter of the stilling well. This menu
item is available if you set "Stilling Well" in menu
item C.1.1 Tank Type.
Minimum access level to change the
setting: Expert
The distance from the flange facing or the
thread stop to the top limit of the measuring
range (a zone given by the user where it is not
possible to measure). We recommend a
minimum blocking distance of 100 mm / 4¨
below the bottom of the antenna. If the
distance is less than the blocking distance, the
device continues to show the blocking distance
on the display screen.
Minimum access level to change the
setting: Expert
Using this function, the device processes several
measurement readings to filter out disturbances.
Increasing the time constant will smoothen the
integrated readings, decreasing will roughen the
readings. s = seconds.
Minimum access level to change the
setting: Expert
www.krohne.com
OPERATION
Selection list
Agitator, Stilling Well,
Process, Storage
min-max:
0.0.
+03
100.00
mm /
0.0...2362.2¨ /
0.0. 196.85 ft
min-max: 0.000.
20.000 m /
0.0...787.40¨ /
0.0. 65.617 ft
min-max:
22.0
.......... 999.0 mm /
-03
866.14
...39.331¨ /
-0.3 ....
72.138
3.2776 ft
min-max:
0.0.
5000.0 mm /
0.0...196.85¨ /
0.0. 16.404 ft
min-max:
0. ... 100.0 sec (seconds)
4
Marine Default
Storage
20000 mm
/ 787.402¨
/ 65.617 ft
1
1.0000 m /
39.370¨ /
3.2808 ft
1
100 mm /
3.937¨
1
260 mm
3 s
45