KROHNE OPTIWAVE-M 7400 C Short Manual page 51

24 ghz radar (fmcw) level transmitter foragitated and corrosive liquids
Table of Contents

Advertisement

OPTIWAVE-M 7400 C
Menu
Function
No.
C5.1.2 Identification
C5.1.2.1
Polling Address
C5.1.2.2
Tag
C5.1.2.3
Long Tag
C5.1.2.4
Manufacturer ID
C5.1.2.5
Device Type
C5.1.2.6
Device ID
C5.1.2.7
Universal
Revision
C5.1.2.8
Device Revision
C5.1.2.9
Software
Revision
C5.1.2.1
Hardware
0
Revision
C5.1.3 Device Information
C5.1.3.1
Descriptor
C5.1.3.2
Message
C5.1.3.3
Date
C5.1.3.4
Cfg. Change
Counter
02/2019 - MA OPTIWAVE-M 7400 C R01 en
Function description
A polling address more than 0 will start HART®
multi-drop mode. If you start HART® multi-
drop mode, the current output stays constant at
4 mA.
Minimum access level to change the
setting: Operator
Use this menu item to change the Tag name. It
can have a maximum of 8 characters. For more
data about the characters available, refer to
Keypad functions
on page 28 (values in menu
items).
Minimum access level to change the
setting: Operator
Use this menu item to change the long Tag
name. It can have a maximum of 32 characters.
For more data about the characters available,
refer to
Keypad functions
on page 28 (values in
menu items).
Minimum access level to change the
setting: Operator
This is the manufacturer ID number given to the
supplier by the HART Foundation.
This is the device type number given to the
supplier by the HART Foundation.
This is the device ID number given to the
supplier by the HART Foundation. This shows
that the HART Foundation registered the
HART® device description (DD) file.
This is the version of the HART protocol used
by the device.
This is the revision number for the HART®
device description.
This is the revision number for the device
software.
This is the revision number for the device
hardware.
You can give a short description (16 characters
maximum) of the device in this menu item.
Minimum access level to change the
setting: Operator
You can give more data in this menu item (32
characters maximum).
Minimum access level to change the
setting: Operator
You can enter the date in this menu item
(Format: Year-Month-Day / YYYY-MM-DD)
Minimum access level to change the
setting: Operator
This function counts the number of changes to
the HART® device settings
www.krohne.com
OPERATION
Selection list
000...063
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
4
Marine Default
0
TANK01
1
2014-01-01
To be set during
commissioning.
51