 CJ1W-OD211 Transistor Output Unit (16 Points)
Name
Model
Rated Voltage
Operating Load Voltage Range
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Circuit Configuration
External connection and terminal-
device variable diagram
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They
are not printed on the Units.
A-24
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
CJ1W-OD211
12 to 24 VDC
10.2 to 26.4 VDC
0.5 A/point, 5.0 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.1 ms max.
0.8 ms max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of
10 mA max.
16 (16 points/common, 1 circuit)
5 VDC 100 mA max.
None
10.2 to 26.4 VDC, 20 mA min.
110 g max.
Output indicator
Signal
name
Jxx_Ch1_Out00
L
Jxx_Ch1_Out02
L
Jxx_Ch1_Out04
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out08
L
Jxx_Ch1_Out10
L
Jxx_Ch1_Out12
L
Jxx_Ch1_Out14
L
COM
12 to 24 VDC
• When wiring, pay careful attention to the polarity of the external power supply. The load may oper-
ate incorrectly if the polarity is reversed.
Signal
name
+V
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
COM
Connec-
Signal
tor pin
name
*
A0
Jxx_Ch1_Out01
L
B0
A1
Jxx_Ch1_Out03
L
B1
A2
Jxx_Ch1_Out05
L
B2
A3
Jxx_Ch1_Out07
L
B3
A4
Jxx_Ch1_Out09
L
B4
A5
Jxx_Ch1_Out11
L
B5
A6
Jxx_Ch1_Out13
L
B6
A7
Jxx_Ch1_Out15
L
B7
A8
+V
B8
NJ-series CPU Unit Hardware User's Manual (W500)