The CPU Unit internally performs initialization when the power to the Controller is turned ON.
The following processing is performed for initialization.
Self diagnosis at startup
Data check
Detecting CJ-series Units
Recording Power Turned ON and
Power Interrupted events
* Refer to the NJ/NX-series Troubleshooting Manual (Cat. No. W503) for information on the following errors:
Power Supply Error, CPU Unit Reset, CPU Unit Watchdog Timer Error, and Incorrect Power Supply Unit
Connected.
Operating Mode at Startup
The system will immediately enter RUN mode if RUN mode (default) is set as the startup operating
mode. The system will immediately enter PROGRAM mode if PROGRAM mode is set as the startup
operating mode.
• RUN Mode Set as Startup Mode
Power
Operating mode
RUN indicator
RUN output on
Power Supply Unit
NJ-series CPU Unit Hardware User's Manual (W500)
Process
CPU Unit Startup
Time at Power ON
Startup
RUN mode
Flashing
Lit
ON
Description
Operation is monitored for the following errors: Power Supply
Error, CPU Unit Reset, CPU Unit Watchdog Timer Error, and
Incorrect Power Supply Unit Connected. *
The _RetainFail (Retention Failure Flag) system-defined variable
changes to TRUE at the following time: when the values of vari-
ables for which the Retain attribute was set to retain the values
and the values in DM, EM, and HR Areas in the memory used for
CJ-series Units were not retained after a power interruption.
The CJ-series Units mounted in the Controller are detected.
The Power Turned ON and Power Interrupted events are
recorded.
• PROGRAM Mode Set as Startup Mode
Power
CPU Unit Startup
Time at Power ON
Operating mode
Startup
RUN indicator
Flashing
RUN output on
Power Supply Unit
4 Installation and Wiring
PROGRAM mode
OFF
OFF
4
4-3