Honeywell Notifier NFW-100X Manual page 105

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Maintenance Programming Level
Pressing 1 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To enable a zone, enter the three digit zone number (000 - 099). After the second digit is
entered, the zone will be enabled and the cursor will return to the original position. The next zone to be enabled can then be entered.
Press Esc (Escape) to return to the previous screen.
Pressing 2 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To disable a zone, enter the three digit zone number (000 - 099). After the second digit is
entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered.
Press Esc (Escape) to return to the previous screen.
Pressing 3 while viewing Zone Setup screen will display the following screens:
Zones 097, 098, 099, and 096 can be programmed for normal zone operation or for special purpose applications. In the above illustra-
tion, the four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning
them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the display to toggle between PAS 97 On and
PAS 97 Off. When Zone 097 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 097
to activate. By assigning Zone 097 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a PAS condition in the control panel. Do not assign Zone 097 to a Notification Appliance Circuit
when using this zone to indicate a PAS condition.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-sig-
nal 98 On and Pre-signal 98 Off. When Zone 098 is programmed On, a Pre-signal activation of any device will cause Zone 098 to acti-
vate. By assigning Zone 098 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 098 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two
Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 77 for a description of this feature.
Pressing 1 while viewing the Special Purpose Zone Screen #2 will cause the display to change to Local Alm 96 On. Each press of the 1
key will cause the display to toggle between Local Alm 96 On and Local Alm 96 Off. When Zone 096 is programmed On, a Local Alarm
activation of any smoke detector will cause Zone 096 to activate. By assigning Zone 096 to a control module in the Programming Zone
Assignment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control
panel. Local Alarm Zone alarms are not reported to the Central Station.
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
ZONE TO ENABLE
Z
ZONE TO DISABLE
Z
SPEC PURPOSE ZONE
1=PAS 97
OFF
2=PRE-SIGNAL 98
OFF
3=TWO STAGE 99
OFF
Special Purpose Screen #1
Enable Screen
Disable Screen
SPEC PURPOSE ZONE
1=LOCAL ALM 96
Special Purpose Screen #2
Programming
OFF
105