Honeywell Notifier NFW-100X Manual page 40

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Installation
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer menu controls. Set the printer options
(under the menu area) as shown in the following table:
PRN-6 Printer Installation
When connected to the FACP via the N-ANN-S/PG module, the PRN-6 prints the status changes within the control panel and time-
stamps the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed
paper. This section contains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as
a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may
be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the N-ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into
the DB-25 connector on the PRN printer and the other end plugs into the parallel connector on the N-ANN-S/PG module. Note that the
9-pin DB-9 port on the N-ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable.
Connect either a serial or parallel printer, but not both at the same time.
Setting Printer Options
Refer to the documentation supplied with the PRN-6 printer for instructions on using the printer menu controls. Set the printer options
(under the menu area) as shown in the following table:
40
Option
Font
LPI
ESC Character
Bidirectional Copy
CG-TAB
Country
Auto CR
Color Option
Formien
Lines
Standard
Barcode
Barcode
Table 2.1 PRN-7 Setup Options
Option
Font
HS Draft
LPI
6 LPI
ESC Character
ESC
Bidirectional Copy
ON
CG-TAB
Graphic
Country
E-US ASCII
Auto CR
OFF
Color Option
Not Installed
Formien
Lines
6LPI=60
Standard
Exec 10.5
Table 2.2 PRN -6 Setup Options
Setting
Option
HS Draft
CPI
6 LPI
Skip
ESC
Emulate
ON
I/O
Graphic
Buffer
E-US ASCII
Serial
OFF
Baud
Not Installed
Format
Protocol
6LPI=60
Character Set
Exec 10.5
SI.Zero
Off
Auto LF
Unsecured
Setting
Option
CPI
Skip
Emulate
I/O
Buffer
Serial
Baud
Format
Protocol
Character Set
SI.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Optional Module Installation
Setting
10CPI
0.5
LQ-2550
64K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
Setting
10CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
12/72"
12/72"
12/72"
12/72"
12/72"
12/72"