Programming
ANN-LED Options
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #2
The first screen indicates that the N-ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Supervisories,
and Troubles for SLC Loop #1 addressable Detectors with addresses 001 through 010. The programming can be changed using ANN-
LED Address Screens 2 and 3.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms for addressable
device addresses 001-030 or Alarms, Supervisories, and Troubles for addressable device addresses 001-010.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated - refer to the tables in
"ANN-LED Zone Option - Alarm Only (for use with N-ANN-RLED module)" on page 94 and "ANN-LED Point Option - Alarm
Only (for use with N-ANN-RLED module)" on page 95.
Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or addressable modules to be annunci-
ated.
ANN-LED Zone Option - Alarm Only (for use with N-ANN-RLED module)
If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the first N-
ANN-LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the
remaining modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED
assignments for each N-ANN-LED module will be as follows.
Alarm Silenced
The LED assignments for the modules annunciating Zone Ranges 060 - 089 and 090 - 099, will follow the same pattern as the second N-
ANN-RLED module.
94
Pressing 2 for Module Options while viewing the (XXX) ANN-BUS Address Screen when the ANN-LED
YES
option is selected, will display the following screen:
ANN-LED - ADDR X-1
SLC 1 DET 001-010
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
NAC 1 Fault
Earth Fault
Battery Fault
Zone 000
Zone 001
Active/Alarm
Active/Alarm
Zone 005
Zone 006
Active/Alarm
Active/Alarm
Zone 010
Zone 011
Active/Alarm
Active/Alarm
Zone 015
Zone 016
Active/Alarm
Active/Alarm
Zone 020
Zone 021
Active/Alarm
Active/Alarm
Zone 025
Zone 026
Active/Alarm
Active/Alarm
Table 3.4 N-ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Zone 030
Zone 031
Active/Alarm
Active/Alarm
Zone 035
Zone 036
Active/Alarm
Active/Alarm
Zone 040
Zone 041
Active/Alarm
Active/Alarm
Zone 045
Zone 046
Active/Alarm
Active/Alarm
Zone 050
Zone 051
Active/Alarm
Active/Alarm
Zone 055
Zone 056
Active/Alarm
Active/Alarm
Table 3.5 N-ANN-RLED Module #2
ANN-LED - ADDR X-1
1=POINT/ZONE
POINT
2=ALARM/ATS
ATS
ANN-LED Address Screen #2
NAC 2 Fault
NAC 3 Fault
Charger Fault
Disabled
Zone 002
Zone 003
Active/Alarm
Active/Alarm
Zone 007
Zone 008
Active/Alarm
Active/Alarm
Zone 012
Zone 013
Active/Alarm
Active/Alarm
Zone 017
Zone 018
Active/Alarm
Active Alarm
Zone 022
Zone 023
Active/Alarm
Active/Alarm
Zone 027
Zone 028
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Zone 032
Zone 033
Active/Alarm
Active/Alarm
Zone 037
Zone 038
Active/Alarm
Active/Alarm
Zone 042
Zone 043
Active/Alarm
Active/Alarm
Zone 047
Zone 048
Active/Alarm
Active Alarm
Zone 052
Zone 053
Active/Alarm
Active/Alarm
Zone 057
Zone 058
Active/Alarm
Active/Alarm
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Master Programming Level
ANN-LED - ADDR X-1
1=RANGE
PT001-010
2=DET/MOD
DET
ANN-LED Address Screen #3
NAC 4 Fault
Maintenance
Zone 004
Active/Alarm
Zone 009
Active/Alarm
Zone 014
Active/Alarm
Zone 019
Active/Alarm
Zone 024
Active/Alarm
Zone 029
Active/Alarm
Not Used
Not Used
Zone 034
Active/Alarm
Zone 039
Active/Alarm
Zone 044
Active/Alarm
Zone 049
Active/Alarm
Zone 054
Active/Alarm
Zone 059
Active/Alarm