Optional Module Installation
Dip Switches
There are two configurable dip switches on the IPOTS-COM communicator.
•
SW2: 6-position dip switch- FUTURE USE- No configuration necessary.
•
SW3: 2-position dip switch- Factory Settings- Do not change unless instructed to do
so by Honeywell.
2.8 Optional Module Installation
WARNING: RISK OF ELECTRIC SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR
WIRING.
2.8.1 CELL-CAB-N/CELL-MOD
The CELL-CAB-N/CELL-MOD offers an optional GSM communicator card for central station reporting. It mounts in its own plastic or
metal enclosure. Use of the CELL-MOD/CELL-CAB-N requires the IPOTS-COM communicator.
Installation
Install the CELL-CAB-N as described in the Product Installation Document #LS10186-001NF-E and the CELL-MOD as described in
#LS10182-000GE-E.
Wiring
Connections are made from TB2 on the IPOTS-COM board to the to terminal on the GSM card as shown below.
2.8.2 PWRMOD24 NAC Expander
The PWRMOD24 is an optional module that provides an additional 3 amps of NAC power.
Installation and Wiring
Install the PWRMOD24 as described in the Product Installation Document #LS10185-000GE-E.
2.8.3 4XTM Transmitter Module Installation
The 4XTM provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A
jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch
allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
IPOTS-COM
B
A
+
-
Figure 2.14 Wiring the CELL-CAB/CELL-MOD
Figure 2.13
IPOTS-COM Dip
Switches
CELL-CAB/CELL-MOD
- + A B
Installation
SW2
SW3
31