5: System; 6: Zone Setup - Honeywell Notifier NFW-100X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Programming
3.7.5 System
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
SYSTEM
1=NACS ENB
1,2,3,4
2=REM SYNC ENAB
System Screen #1
Pressing 1 while viewing NAC Screen #1 will cause the display to change to NAC1 Yes. This will allow the selected main circuit board
NAC to activate its devices. Each press of the 1 key will cause the display to toggle between NAC1 Yes and NAC1 No. The same action
is performed for the other 3 NAC circuits by selecting the number of the desired output circuit.
To enable remote synchronization, press the 3 key while viewing System Screen #2. Each press of the key will toggle the screen between
Rem Sync Enab Yes and Rem Sync Enab No.
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
3=4XTM SPV ENAB
System Screen #2
To change the time, press 1 to display the following screen:
A flashing cursor will appear on the left side of the display. Enter the four digit number corresponding to the time (0000 - 1259). When
the fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The
display will return to the Time and Date Screen displaying the new time.
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and two digit year. The cursor will
move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and
Date Screen which will show the new date.
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
3=4XTM SPV ENAB
System Screen #2
means there is a 4XTM installed. Each press of the 1 key will cause the display to toggle between 4XTM Spv Enab. No and 4XTM Spv
Enab. Yes.
3.7.6 Zone Setup
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
104
Pressing 2 while viewing Maintenance Screen #2, will display the following screen:
SYSTEM
1=NACS ENAB
2=REM SYNC ENAB YES
System Screen #1
Pressing 1 while viewing System Screen #1 will display the following:
YES
Pressing 1 while viewing System Screen #2 will cause the following screen to be displayed:
YES
NO
To enable the onboard battery charger, press the 2 key while viewing System Screen #2. Each press of the
key will toggle the screen between Charger Enab Yes and Charger Enab No. The setting must say Charger
YES
Enb No when an external battery charger is being used.
NO
If a 4XTM Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 3 while viewing System Screen #2 will cause the display to toggle to 4XTM Spv Enab. Yes, which
Pressing 3 while viewing Maintenance Screen #2 will display the following screen:
1,2,3,4
ENABLE NACS
1=NAC1
N
3=NAC3
2=NAC2
N
4=NAC4
Disable NACs Screen
TIME AND DATE
1=TIME
01:00 AM
2=DATE
05-04-2017
3=CLOCK FORMAT 12HR
Time and Date Screen
ENTER TIME
01:00 AM
1=AM
2=PM
Time Screen
ENTER DATE
MONTH DAY YEAR
05-04-17
Date Screen
ZONE SETUP
1=ENABLE
2=DISABLE
3=SPECIAL PURPOSE
Zone Setup Screen
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Maintenance Programming Level
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
YES
3=4XTM SPV ENB
YES
System Screen #2
N
N