Master Programming Level
As an example, the user could quickly enter 'FLR_3_ROOM 305' as follows:
1.
The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3
2.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor
automatically jumps from the first to the last letter of the Noun field
3.
With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4.
Press the right arrow key to advance the zone field
5.
Select a zone number from 000 to 099. Z000 (default zone) is the general alarm zone. Z001 through Z099 may be selected to link
software zones
Edit Module Screen for Control Modules
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed-in, if the selected address corresponds
to a control module, a screen displaying information about the control module with the selected address will be displayed as illustrated in
the following:
In the preceding example:
 Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the
control panel (enabled)
 <ADJ><NOUN> - represents the adjective and noun, which have been programmed, describing the location of the displayed
device
 Control - indicates that the selected module is a control module
 S or * - represents Silenceable (S) or Nonsilenceable (*)
 W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled)
 ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number
from 000 - 099)
 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module and 002 = Module Address 02)
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Control screens:
EDIT CONTROL
1=ENABLED
YES
2=TYPE CONTROL
3=SILENCEABLE
YES
Edit Control Screen #2
Enable/Disable Module
EDIT CONTROL
1=ENABLED
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
Control Type
EDIT CONTROL
1=ENABLED
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
The programmer can change a module's existing or factory default programming by pressing 3 in the Mod-
ules Screen. The following screen will be displayed:
ENTER MODULE ADDRESS

NORMAL
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
000    
Edit Control Screen #3
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2. Each
YES
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the
module will not be polled by the control panel, preventing the module from activating its output devices.
YES
The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices
are disabled.
To select the type of control module being programmed, press the 2 key while viewing the Edit Control
YES
Screen #2. This will cause the control panel to display the following Control Type Screens. Press the down
arrow key to view additional screens and selections.
YES
FUTURE USE
2=BELL-CIRCUIT
3=HORN-CIRCUIT
EDIT MODULE
Edit Module Screen
CONTROL
<ADJ><NOUN>
ZNNN
1M002
 
Edit Control Screen #1
EDIT CONTROL
YES
1=NOUN/ADJECTIVE
2=DESCRIPTION

Edit Control Screen #4
CONTROL TYPE
Control Type Screen #1
Programming
EDIT CONTROL
1=MNS OVERRIDE
NO
2=CTRL MOD DLY
NO
WIRELESS
NO
Edit Control Screen #5
65