2=Point Program; Detector Programming - Honeywell Notifier NFW-100X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Master Programming Level
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop sim-
ilar to the following display:
In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control
modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
3.6.2 Point Program
PROGRAMMING
1=AUTOPROGRAM

2=POINT PROGRAM

3=ZONE SETUP
Programming Screen #1

Detector Programming

Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an address-
able detector. The following screen will be displayed by the control panel:
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector
address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such
as 005. The screen will then ask whether the detector being added is wireless.
Select 1 for wired detector or 2 for wireless detector. When the choice is selected, the following screen will be displayed:
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the
newly added detector. If the selected detector is a multi-criteria Photo (Fire)/CO detector, select 1 for Fire CO. When the type has been
selected, the following screen will be displayed:
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
The Point Program option allows the programmer to add a new addressable device to the SLC loop, delete
an existing device from the loop or change the programming for an existing device. Pressing 2, while view-
ing Programming Screen #1, will select the Point Program option and display the following screens:
POINT PROGRAM
1=DETECTOR
2=MODULE
Point Program Screen
1=ADD
2=DELETE
3=EDIT
ENTER DETECTOR#

1=DETECTOR
2=DETECTOR:WIRELESS
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
DETECTOR#
IS ADDED
SELECT TYPE
DETECTOR
Detector Screen
ADD DETECTOR
Add Detector Screen
ADD DETECTOR
Add Detector Screen
DETECTOR TYPE
1=FIRE CO
through
2=USED-DEFINED-12
ADD DETECTOR
005
Programming
53

Advertisement

Table of Contents
loading