Master Programming Level
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ANN-I/O Options
Pressing 2 for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the follow-
ing screen:
ANN-I/O - ADDR X-1
SLC 1 DET 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
The first screen indicates that the ANN-I/O at ANN-BUS address 1 is programmed to annunciate SLC Loop #1 addressable Detectors
with addresses 1 through 30. The programming can be changed using ANN-I/O Address Screens 2 and 3.
Pressing 1 while viewing ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information.
Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in "ANN-
I/O Zone Option" on page 92 and "ANN-I/O Point Option" on page 93).
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated.
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE
ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen
ANN-I/O - ADDR X-1
1=POINT/ZONE
POINT
ANN-I/O Address Screen #2
ANN-I/O - ADDR X-1
1=RANGE
PT001-030
2=DET/MOD
DET
ANN-I/O Address Screen #3
Programming
91