5-1
Diagnostics and Fault Finding

Chapter 5 Diagnostics and Fault Finding

DIAGNOSTIC LEDS

LED1
POWER ON
LED2
STALL TRIP
LED3
OVERCURRENT
LED4
PLL LOCK
LED5
CURRENT LIMIT
Illuminated when the Auxiliary Supply is energised.
Illuminated when the Controller has detected a Stall or
Current Limit Condition for more than 60 seconds.
Illuminated when the Armature Current exceeds
approximately 3½ times Calibrated Current.
Illuminated when the Main AC Supply is energised
and the Electronic Phase Lock Loop is Synchronised.
Illuminated when the Controller is in Current Limit and
Speed Control is lost, i.e. a stall condition, after 60
seconds the controller will trip.
A1 A2 A3 A4
DI AGN OSTI C LEDS
L1 POWER ON
L2 STALL TRIP
L3 OVERCURRENT
L4 PLL LOCK
L5 CURRENT LIMIT
SW1
ON
1
1 2 3 4 5 6 7 8 9 10
SW2 SW3
SW4
FL1 FL2 F- F+
RAMP UP
RAMP DOWN
SPEED PROPORTIONAL
SPEED INTEGRAL
CURRENT LIMIT
CURRENT PROPORTIONAL
CURRENT INTEGRAL
IR COMP ENSATION
MAX SPEED CALI BRATION
ZERO SPEED ADJUST
ZERO SPEED THRES HOLD
L2/ N
L1
A+
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
A-