Page 1
Parker SSD Drives company without written permission from Parker SSD Drives, a division of Parker Hannifin Ltd . Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to make amendments or correct omissions.
Page 2
WWW.SDS.LTD.UK | 0117 9381800 Safety Information Requirements Please read this information BEFORE installing the equipment. IMPORTANT: Intended Users This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation.
Page 3
WWW.SDS.LTD.UK | 0117 9381800 Safety Information Product Warnings Caution Caution Earth/Ground Risk of Refer to Protective electric document Conductor shock ation Terminal Hazards DANGER! - Ignoring the following may result in injury 1. This equipment can endanger life by 5. For measurements use only a meter exposure to rotating machinery and to IEC 61010 (CAT III or higher).
Page 4
WWW.SDS.LTD.UK | 0117 9381800 Safety Information WARNING! - Ignoring the following may result in injury or damage to equipment SAFETY Where there is conflict between EMC and Safety requirements, personnel safety shall always take precedence. • Never perform high voltage resistance •...
Page 5
WWW.SDS.LTD.UK | 0117 9381800 Safety Information CAUTION! APPLICATION RISK • The specifications, processes and circuitry described herein are for guidance only and may need to be adapted to the user’s specific application. We can not guarantee the suitability of the equipment described in this Manual for individual applications.
R O D U C T V E R V I E W Description....................1-1 Product Range ....................1-1 Chapter 2 506/507/508 V E R V I E W O F T H E • User Supplied Primary Components ............2-1 •...
Page 7
A I N T E N A N C E A N D E P A I R Routine Maintenance..................5-1 Repair ......................5-1 Returning the Unit to Parker SSD Drives..............5-1 Chapter 6 506/507/508 E R T I F I C A T I O N F O R T H E Certificates ......................6-2...
RODUCT VERVIEW Description The 506/507/508 series controllers are compact, non-isolated motor speed controllers specifically designed for dc shunt would and permanent magnet motors. The controllers are intended to operate from a single phase AC mains supply in the ranges 110/120V AC or 220/240V AC 50/60Hz.
This is a non-isolated product. The control connections are not isolated from the AC supply. Any connection to earth or use of earth (ground) referenced components either deliberately or unintentionally will cause permanent damage to the controller. 506/507/508 - HA389427...
Collector * Health Health Output 24V at 50mA open Collector * Zero Speed Level Zero Speed Output For other levels see Table 3.1 Level Trim Auxiliary Setpoint Auxiliary Direct Speed +10V @ 100K Full Setpoint Speed Input 506/507/508 - HA389427...
The zero speed detector operates from the Controller Output voltage, the default level is set to 6% of 180V dc. Switches Switch Imax. 506 - 0.25 to 1.5A Imax. 506 - 0.5 to 3.0A Imax. 507 - 0.5 to 3.0A Imax.
Installing the 506/507/508 506/507/508 NSTALLING THE Installation Speed Control Figure 4.1 Wiring Diagram Speed Control Fuse Fuse MAINS L2/N FILTER I LIMIT + 10 V SETPOINT COMMON neutral Double/reinforced insolation boundary provided by users TACHO GENERATOR potentiometer and run switch Additional line fuse recommended for applications where live connections are made rather than live and netral.
Installing the 506/507/508 WARNING! Ensure that all wiring is electrically isolated and cannot be made "live" unintentionally by other personnel. Wire Sizes * Contains semiconductor fuses as recommended below. Model Maximum Function Cable AC Supply SSD Drives Fuse Output (Wire) Size...
Short Circuit Rating The 506 and 507 controllers are suitable for use on a circuit capable of delivering not more than 1000 RMS symmetrical amperes, 240V maximum; whilst the 508 controller is suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical amperes, 240V maximum.
Installing the 506/507/508 Installing the 506/507/508 Block Diagram TRANSFORMER SELECTION SWITCH +12V 220/240 LED 1 110/120 POWER POWER QUENCH SUPPLY -10V REF +10V REF -12V 0V COMMON LED 2 HEALTH +16V DRIVE STALL HEALTH HEALTHY PROTECTION TORQUE / TORQUE/CURRENT LIMIT 10V = 100%...
Installing the 506/507/508 Terminal Tightening Torque Refer to the Terminal Tightening torque table shown on page 4-2 for both the Power and Control Terminals. Field Grounding Terminals The field grounding terminals are identified with the International Grounding Symbol (IEC Publication 417, Symbol 5019).
Installing the 506/507/508 IP20 80 mm 80 mm 90 mm 84 mm 84 mm 84 mm 140 mm 140 mm 140 mm 105 mm 105 mm 105 mm 50 mm 50 mm 50 mm 140 mm 140 mm 140 mm...
Installing the 506/507/508 Filter Figure 4.4 Filter Mechanical Arrangement LINE L2 L1 PE END USER TO AFFIX OWN DIN RAIL HERE TO MOUNT DRIVE 4 x M5 Inserts for DIN Rail Mounting at chosen height 200mm 4 Holes M6 Clearance...
Installing the 506/507/508 EMC Connections Figure 4.5 Wiring Diagram Mains Filter Screened Cable DC Motor Product AC Supply Filter Grd (PE) Grd (PE) Grd (PE) Installation and Set-Up Warning Before applying power check:- Switch Selection (a) Mains switch set to intended supply voltage, Left 110/120, Right 220/240 (b) Personality switches.
4-10 Installing the 506/507/508 Note: Even when intending to utilise tachogenerator feedback it may be wise to initially run under armature control. Set feedback voltage switches accordingly. Note that if this procedure is followed the tachogenerator must be temporarily disconnected as it will affect operation of the controller.
Page 26
4-11 Installing the 506/507/508 If the controller is in “Tacho” control then excess speed is due to incorrect polarity of feedback. Alter wiring as follows:- Problem Action Direction correct but Reverse Tachogenerator polarity only. overspeeding. Direction incorrect and overspeeding. Reverse field polarity only.
4-12 Installing the 506/507/508 Fault Finding Problem Possible Cause Remedy Controller will not Wrong supply voltage. Check setting on mains switch. power up - no ‘on’ It is likely that if too high a indication. voltage has been used the...
Page 28
4-13 Installing the 506/507/508 Problem Possible Cause Remedy Motor will not run at Wrong speed range Refer to Installation and Set-up correct maximum selection on preset chapter. speed. switches. Stall light comes on Incorrect wiring of run Run contact should be wired after 15 seconds in contact.
Page 29
4-14 Installing the 506/507/508 506/507/508 - HA389427...
• The model and serial number - see the unit’s rating label • Details of the fault Contact your nearest Parker SSD Drives Service Centre to arrange return of the item. You will be given a Returned Material Authorisation. Use this as a reference on all paperwork you return with the faulty item.
Page 31
Routine Maintenance and Repair 506/507/508 - HA389427...
IN T HE OVERALL PRODUCT J UST IFICAT ION SSD = SSD DRIVES LIMITED Figure 6-1 Parker SSD Drives EMC `CE' Mark Validity Chart For more information refer to HA388879 EMC Installation Guidelines for Modules and Systems available from your local Parker SSD Drives office.
2006/95/EC the EMC accordance with the Directive when low voltage We Parker SSD Drives, address as below, We Parker SSD Drives, address as below, the unit is used directive for declare under our sole responsibility that the declare under our sole responsibility that the...
All control terminals are at a potential of the peak of the input supply with respect to earth (ground) All cables should be rated for this voltage. Parameter Symbol Value Units Overspeed limiting Standard Type of controller Fixed proportional plus integral Feedback method Non-isolated shunt Linearity 506/507/508 - HA389427...
Above 1000m derate at 1% / 100m Atmosphere Non-flammable, non-corrosive and dust free Storage Temperature Range C to +55 Transport Temperature Range -25 C to +55 Enclosure IP2X suitable for cubicle mounting Installation Category Overvoltage Category III. Pollution Pollution Degree 2. 506/507/508 - HA389427...
Supply Filter. * Achieved with up to 50m of motor cable. Port Phenomenon Test Standard Level Generic Standard Enclosure Port Radiated EN55011 Class B EN50081-1 (1992) Power Port Conducted EN55011 Class B* EN50081-2 (1994) 506/507/508 - HA389427...
Field Voltage (0.9 x Vs) V dc 110/120V AC 90-100 220/240V AC 180-200 Adjustment Ranges Range selected by built in switches. Parameter Maximum current * (l max, A) 0.25 - 3 0.5 - 6 1 - 12 506/507/508 - HA389427...
Technical Specification Product Code Block Product Code Feature Basic Product 3 Amp 6 Amp 12 Amp Livery Standard 01 to 99 Customer Cover IP20 Cover Special Options Standard 01 to 99 Documented Special Options 506/507/508 - HA389427...
Page 39
Company name change 18354 19/07/05 Certificate updated on page 6-2 Cover removal improved, page 4-8 19650 17/10/06 Ambient temperature amended 20002 20/06/07 New company name (19591) FIRST USED ON MODIFICATION RECORD 506/507/508 Product Manual DRAWING NUMBER SHT. 2 ZZ389427 OF 2...