3.
Edit the U_BMS.txt file
3
# 1
# 2
# ...
Edit the U_BMS.txt file, on the controller microSD card, to setup
the controller Modbus RTU interface.
Available settings (default in bold):
BMS Slave address: 1 to 247
BMS Baud rate: 19200 or 9600
BMS Parity: even, odd, no (or none)
Heat pump integration via BMS: off or on
on = enables dynamic heat curve offset in integrated heat
pump, and integrated heat pump defrost state.
Exclude zone from heat curve offset calculation:
0, or 1 through 12 (0 = no channel)
Select master channels of the zones (lowest numbered
channel in the zone) to exclude.
The zone subchannels follow the state of the master
channel.
Example: 3,5,12 = exludes channels with master channels
3, 5 and 12.
Bypass zone: 0, or 1 to 12 (0 = no channel, example: 3,12)
Select master channels of the zones (lowest numbered
channel in the zone) to bypass, MAXIMUM 2 channels.
The zone subchannels follow the state of the master
channel.
Example: 4,12 = bypasses zones with master channels 4
and 12.
Ceiling cooling channel: 0, or 1 to 12 (0 = no channel,
example: 1,4,10)
Select the channels which controls ceiling cooling in the
zones. The zone subchannels will not follow the state of the
master channel.
Example: 1,4,10 = set ceiling cooling to channels 1, 4 and
10.
BMS Temperature format: c or f
c = Celsius, f = Fahrenheit
Repeat for each Base PRO controller in the system.
4.
Connect the controllers
4
Slave 1
Connect the controllers to each other using the Base PRO
controller system device bus.
4
|
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
U_BMS.txt
U_BMS.txt
U_BMS.txt
Slave 2
Slave ...
5.
Connect the Base PRO system
5
Slave 1
Slave 2
Slave 1
Slave ...
Connect the Base PRO system to the BMS.
SI0000218

1.3 Connecting to the BMS cable

Caution!
Depending on EMC conditions in the installation, and/or
distance between the devices, the "-" connection on the
Base PRO controller might be needed.
1
2
X-148
3
SI0000219
The illustrations above show how to connect a BMS to the Modbus
RTU interface on the controller.
|
Installation manual
BMS
Slave 2
X-148
BMS
A
B
+ -
A
B
+
-
A
B
+
-
A
B
X-148
Slave ...
SI0000220
SI0000221
-
A
B
-
SI0000222
SI0000223