Uponor Smatrix Base PRO X-148 Installation Manual page 12

Modbus rtu
Table of Contents

Advertisement

Examples:
Request example:Write 23 ˚C (73.4 ˚F = value 734, 0x02DE) setpoint, channel 5
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Response example:Write 23 ˚C (73.4 ˚F = value 734, 0x02DE) setpoint, channel 5
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Request example:Write 25 ˚C (77.0 ˚F = value 770, 0x0302) maximum floor temperature limit, channel 12
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Response example:Write 25 ˚C (77.0 ˚F = value 770, 0x0302) maximum floor temperature limit, channel 12
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Request example:Write 12 % comfort setting, channel 12
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Response example:Write 12 % comfort setting, channel 12
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Request example:Write 5 ˚C (41.0 ˚F = value 410, 0x005A) heating/cooling offset temperature
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
Response example:Write 5 ˚C (41.0 ˚F = value 410, 0x005A) heating/cooling offset temperature
Slave address
Function code
(0x01)
(0x06)
1 byte
1 byte
12
|
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Starting register
Starting register
address HI
address LO
(0x00)
Start at 5 (0x04)
1 byte
1 byte
Output address to
Output address to
write HI
write LO
(0x00)
Start at 5 (0x04)
1 byte
1 byte
Starting register
Starting register
address HI
address LO
(0x00)
Start at 59 (0x3A)
1 byte
1 byte
Output address to
Output address to
write HI
write LO
(0x00)
Start at 59 (0x3A)
1 byte
1 byte
Starting register
Starting register
address HI
address LO
(0x00)
Start at 72 (0x47)
1 byte
1 byte
Output address to
Output address to
write HI
write LO
(0x00)
Start at 72 (0x47)
1 byte
1 byte
Starting register
Starting register
address HI
address LO
(0x00)
Start at 73 (0x48)
1 byte
1 byte
Output address to
Output address to
write HI
write LO
(0x00)
Start at 73 (0x48)
1 byte
1 byte
|
Installation manual
Register value HI
Register value LO
(0x02)
(0xDE)
1 byte
1 byte
Output value written
Output value written
HI
LO
(0x02)
(0xDE)
1 byte
1 byte
Register value HI
Register value LO
(0x03)
(0x02)
1 byte
1 byte
Output value written
Output value written
HI
LO
(0x03)
(0x02)
1 byte
1 byte
Register value HI
Register value LO
(0x00)
(0x0C)
1 byte
1 byte
Output value written
Output value written
HI
LO
(0x00)
(0x0C)
1 byte
1 byte
Register value HI
Register value LO
(0x00)
(0x5A)
1 byte
1 byte
Output value written
Output value written
HI
LO
(0x00)
(0x5A)
1 byte
1 byte
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes

Advertisement

Table of Contents
loading

Table of Contents