Frame Format: Write Single Coil; Frame Format: Write Single Holding Register - Uponor Smatrix Base PRO X-148 Installation Manual

Modbus rtu
Table of Contents

Advertisement

2.5 Frame format: Write Single Coil

Request
Slave address
Function code
(0x01 – 0xF7)
(0x05)
1 byte
1 byte
Response
Slave address
Function code
(0x01 – 0xF7)
(0x05)
1 byte
1 byte
Response in case of error
Slave address
Error code
(0x01 – 0xF7)
(0x85)
1 byte
1 byte
Example:
Request example:Change state from ECO to Comfort
Slave address
Function code
(0x01)
(0x05)
1 byte
1 byte
Response example:Change state from ECO to Comfort
Slave address
Function code
(0x01)
(0x05)
1 byte
1 byte

2.6 Frame format: Write Single Holding Register

Request
Slave address
Function code
(0x01 – 0xF7)
(0x06)
1 byte
1 byte
Response
Slave address
Function code
(0x01 – 0xF7)
(0x06)
1 byte
1 byte
Response in case of error
Slave address
Error code
(0x01 – 0xF7)
(0x86)
1 byte
1 byte
Starting register address
(0x0000 – 0xFFFF)
2 bytes
Output address to write
(0x0000 – 0xFFFF)
2 bytes
Exception code
(01, 02, 03, 04, or 06)
1 byte
Starting register
Starting register
address HI
address LO
(0x00)
Register 2 (0x01)
1 byte
1 byte
Output address to
Output address to
write HI
write LO
(0x00)
Register 2 (0x01)
1 byte
1 byte
Starting register address
(0x0000 – 0xFFFF)
2 bytes
Output address to write
(0x0000 – 0xFFFF)
2 bytes
Exception code
(01, 02, 03, 04, or 06)
1 byte
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Output value to write
(0xFF00 = 1, 0x0000 = 0)
2 bytes
Output value written
(0xFF00 = 1, 0x0000 = 0)
2 bytes
Output value to write
Output value to write
HI
LO
(0x00)
(0x00)
1 byte
1 byte
Output value written
Output value written
HI
LO
(0x00)
(0x00)
1 byte
1 byte
Register value
(0x0000 – 0xFFFF)
2 bytes
Output value written
(0x0000 – 0xFFFF)
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
CRC
2 bytes
|
Installation manual
|
11

Advertisement

Table of Contents
loading