Discrete Input Data Points - Uponor Smatrix Base PRO X-148 Installation Manual

Modbus rtu
Table of Contents

Advertisement

Display name
Room setpoint override,
cannel 4
Room setpoint override,
cannel 5
Room setpoint override,
cannel 6
Room setpoint override,
cannel 7
Room setpoint override,
cannel 8
Room setpoint override,
cannel 9
Room setpoint override,
cannel 10
Room setpoint override,
cannel 11
Room setpoint override,
cannel 12
* Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. It
takes about 2 minutes for the actuators in the Base PRO system to be fully
opened.

3.4 Discrete Input data points

These datapoints are read only and show the actuator, pump/boiler,
and GPI status on the controller (binary, on/off).
Display name
Actuator status/channel 1
(bit 0)
Actuator status/channel 2
(bit 1)
Actuator status/channel 3
(bit 2)
Actuator status/channel 4
(bit 3)
Actuator status/channel 5
(bit 4)
Actuator status/channel 6
(bit 5)
Actuator status/channel 7
(bit 6)
Register
Physical
address
address
(decimal)
(decimal)
00033
00032
00034
00033
00035
00034
00036
00035
00037
00036
00038
00037
00039
00038
00040
00039
00041
00040
Register
Physical
address
address
(decimal)
(decimal)
10001
10000
10002
10001
10003
10002
10004
10003
10005
10004
10006
10005
10007
10006
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Function
Type
code (Hex)
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
0x01
Read
0x05
Write
0x0F
Write
multiple
Function
Type
code (Hex)
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
Analogue/
Coding
Binary
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Binary
Unsigned.
0 = Setpoint override disabled (default)
1 = Setpoint override enabled
Analogue/
Coding
Binary
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
|
Installation manual
|
19

Advertisement