Display name
Comfort setting, channel 7
Comfort setting, channel 8
Comfort setting, channel 9
Comfort setting, channel 10
Comfort setting, channel 11
Comfort setting, channel 12
Heating/cooling offset
temperature
Relative humidity (RH) dead
zone (hysteresis)
Relative humidity (RH)
setpoint, channel 1
Relative humidity (RH)
setpoint, channel 2
Relative humidity (RH)
setpoint, channel 3
Relative humidity (RH)
setpoint, channel 4
Relative humidity (RH)
setpoint, channel 5
Relative humidity (RH)
setpoint, channel 6
Register
Physical
address
address
(decimal)
(decimal)
40067
40066
40068
40067
40069
40068
40070
40069
40071
40070
40072
40071
40073
40072
40074
40073
40075
40074
40076
40075
40077
40076
40078
40077
40079
40078
40080
40079
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Function
Type
code (Hex)
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
Analogue/
Coding
Binary
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 = off, 5 - 12 = 5 - 12 %
default: 0.
Analogue
Signed 16 bit integer.
Range: 0 - 5 °C
default: 2 °C (2 °F).
Analogue
Unsigned 16 bit integer.
Range: 2 - 20 = 2 - 20 %
default: 5 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
|