Uponor Smatrix Base PRO X-148 Installation Manual page 20

Modbus rtu
Table of Contents

Advertisement

Display name
Actuator status/channel 8
(bit 7)
Actuator status/channel 9
(bit 8)
Actuator status/channel 10
(bit 9)
Actuator status/channel 11
(bit 10)
Actuator status/channel 12
(bit 11)
Pump/Boiler (bit 12)
GPI status (bit 13)
Relative humidity (RH)
cooling shutdown, channel 1
Relative humidity (RH)
cooling shutdown, channel 2
Relative humidity (RH)
cooling shutdown, channel 3
Relative humidity (RH)
cooling shutdown, channel 4
Relative humidity (RH)
cooling shutdown, channel 5
Relative humidity (RH)
cooling shutdown, channel 6
Relative humidity (RH)
cooling shutdown, channel 7
Relative humidity (RH)
cooling shutdown, channel 8
Relative humidity (RH)
cooling shutdown, channel 9
Relative humidity (RH)
cooling shutdown, channel
10
Relative humidity (RH)
cooling shutdown, channel
11
Relative humidity (RH)
cooling shutdown, channel
12
20
|
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Register
Physical
address
address
(decimal)
(decimal)
10008
10007
10009
10008
10010
10009
10011
10010
10012
10011
10013
10012
10014
10013
10015
10014
10016
10015
10017
10016
10018
10017
10019
10018
10020
10019
10021
10020
10022
10021
10023
10022
10024
10023
10025
10024
10026
10025
Function
Type
code (Hex)
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
0x02
Read
|
Installation manual
Analogue/
Coding
Binary
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.1 = ON, 0 = Off.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Binary
Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.