Holding Register Data Points - Uponor Smatrix Base PRO X-148 Installation Manual

Modbus rtu
Table of Contents

Advertisement

Display name
Humidity data, channel 8
Humidity data, channel 9
Humidity data, channel 10
Humidity data, channel 11
Humidity data, channel 12
Floor temperature data,
channel 1
Floor temperature data,
channel 2
Floor temperature data,
channel 3
Floor temperature data,
channel 4
Floor temperature data,
channel 5
Floor temperature data,
channel 6
Floor temperature data,
channel 7
Floor temperature data,
channel 8
Floor temperature data,
channel 9
Floor temperature data,
channel 10
Floor temperature data,
channel 11
Floor temperature data,
channel 12
Thermostat loss
Dynamic heat curve offset in
integrated heat pump*
* Requires Heat Pump Integration via BMS to be activated in U_BMS.txt.

3.6 Holding Register data points

Note
All temperature data is sent in tenths of either Celsius or
Fahrenheit, depending on the setting in U_BMS file.
Note
0x7FFF is returned if no data is available for the channel.
These datapoints can be both read or written, and contain
temperature setpoint and max/min temperature limits for each
channel (1 to 12) on the controller.
22
|
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Register
Physical
address
address
(decimal)
(decimal)
30021
30020
30022
30021
30023
30022
30024
30023
30025
30024
30026
30025
30027
30026
30028
30027
30029
30028
30030
30029
30031
30030
30032
30031
30033
30032
30034
30033
30035
30034
30036
30035
30037
30036
30038
30037
30039
30038
Function
Type
code (Hex)
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
0x04
Read
|
Installation manual
Analogue/
Coding
Binary
Analogue
Unsigned 16 bit integer.
0-100 % relative humidity
Analogue
Unsigned 16 bit integer.
0-100 % relative humidity
Analogue
Unsigned 16 bit integer.
0-100 % relative humidity
Analogue
Unsigned 16 bit integer.
0-100 % relative humidity
Analogue
Unsigned 16 bit integer.
0-100 % relative humidity
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Analogue
Signed 16 bit integer.
Binary
Unsigned.
1 = Thermostat loss, 0 = No alarm.
Analogue
Signed 16 bit integer.
+10 = 000A
+1 = 0001
0 = 0000
-1 = 00FF
-10 = 00F6