Uponor Smatrix Base PRO X-148 Installation Manual page 28

Modbus rtu
Table of Contents

Advertisement

Display name
Relative humidity (RH)
setpoint, channel 7
Relative humidity (RH)
setpoint, channel 8
Relative humidity (RH)
setpoint, channel 9
Relative humidity (RH)
setpoint, channel 10
Relative humidity (RH)
setpoint, channel 11
Relative humidity (RH)
setpoint, channel 12
28
|
Uponor Smatrix Base PRO Controller X-148 Modbus RTU
Register
Physical
address
address
(decimal)
(decimal)
40081
40080
40082
40081
40083
40082
40084
40083
40085
40084
40086
40085
Function
Type
code (Hex)
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
0x03
Read
0x06
Write
0x10
Write
multiple
|
Installation manual
Analogue/
Coding
Binary
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %
Analogue
Unsigned 16 bit integer.
Range: 0 - 100 = 0 - 100 %
default: 75 %