4.3.7

Designation of Interrupt Input Signal for DVIT Instruction

The interrupt input signal of the interrupt positioning (DVIT) instruction depends on the pulse output
destination device as shown in the following table.
Use an FX
3UC
Use an FX
/FX
3U
Pulse output
destination
device
Y000
Y001
Y002
*1
Y003
*1.
Y003 is available only when two high-speed output special adapters are connected to the FX
Designation of interrupt input using M8336 interrupt input specification function:
1) Turn on M8336.
2) Set the interrupt input number (X000 to X007) in D8336, or specify the user interrupt input command
D8336=H
Setting value
0
1
7
*2
8
9 to E
*4
F
B - 62
PLC User's Manual - Positioning Control Edition
PLC Ver. 1.30 or later to use the interrupt input specification function.
PLC Ver. 2.20 or later to set the user interrupt input command.
3UC
If it is not necessary to use the
interrupt input specification function
(M8336 = OFF), or if an FX
below Ver. 1.30 is used
X000
X001
X002
X003
Interrupt input for Y000
(pulse output destination device)
Interrupt input for Y001
(pulse output destination device)
Interrupt input for Y002
(pulse output destination device)
Interrupt input for Y003
(pulse output destination device)
Specifies X000 for the interrupt input signal.
Specifies X001 for the interrupt input signal.
Specifies X007 for the interrupt input signal.
interrupt input command
Specifies the user
Pulse output destination device
Y000
Y001
Y002
Y003
Do not specify these values.
Set "F" for a pulse output destination device if the device is not used for the interrupt
positioning (DVIT) instruction.
For operation of DVIT instruction, refer to Chapter 9.
Interrupt input signal
If it is necessary to use the interrupt input specification
PLC
3UC
D8336=H
For specifying the settings, refer to the following description.
Description of setting
*2
User interrupt input command
*3
4 Before Programming
4.3 Various Special Relays for Operation Commands
function (M8336 = ON)
Interrupt input for Y000
(pulse output destination device)
Interrupt input for Y001
(pulse output destination device)
Interrupt input for Y002
(pulse output destination device)
Interrupt input for Y003
(pulse output destination device)
for the interrupt input signal.
M8460
M8461
M8462
M8463
PLC.
3U
*2
.

Advertisement