Mitsubishi Electric Melsec-F FX3GC Series User Manual page 139

Hide thumbs Also See for Melsec-F FX3GC Series:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Built-in Positioning Functions
2. Stop of operation
Turn off the reverse rotation (JOG-) switch (X013) to stop the operation in the reverse rotation direction.
1) LED indicator lamp check
Check the LED indicator lamps of the PLC or the display module to check whether or not the outputs are
turned on. The status of each output should be as shown in the following table:
If the transistor outputs of
main unit are used
If the high-speed output
special adapter is used
2) Current value register (D8341, D8340) check
Monitor the current value register (D8341, D8340) of the FX
programming tool, and confirm that the value is not being decreased.
11
Check the operation of the reverse rotation limit switch.
During operation in the reverse rotation direction (at step 10), turn off the reverse rotation limit
switch 1 (X011), and confirm that the operation in the reverse rotation direction is stopped.
The LED indicator lamps and the current value register (D8341, D8340) will change to the same
statuses as the stop statuses described in step 10.
In addition, the "Instruction execution abnormal end" flag (M8329) will turn on.
PLC User's Manual - Positioning Control Edition
Pulse output
method
"Pulse train + direc-
tion" method
"Pulse train + direc-
tion" method
Forward rotation
pulse train (FP)
Reverse rotation
pulse train (RP)
For details on the current value register, refer to Subsection 4.4.1.
For details on the current value register, refer to Subsection 4.4.1.
LED lamp
Status of LED lamp (output)
of output
The LED indicator lamp (turned on and
Y000
off at high speed) will be turned off.
Y004
Kept OFF.
The LED indicator lamp (turned on and
Y0/2
off at high speed) will be turned off.
Y4/6
Kept OFF.
Y0/2
Kept OFF.
The LED indicator lamp (turned on and
Y4/6
off at high speed) will be turned off.
/FX
/FX
/FX
3S
3G
3GC
5 Operation Test
5.1 Test Procedure
/FX
PLC using the
3U
3UC
B - 95