Power-limited Wiring Requirements

2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram
for the SFP-2404 is illustrated below.
Power-limited Circuits
+
Nonreset
J9
J7
AC Power
Figure 2.9 Typical UL Power-limited Wiring Requirements
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
-
+
-
A+
A-
A+
A-
A+
A-
A+
Resettable
CLASS A CLASS A
CLASS A CLASS A
NAC 1
NAC 2
ZONE 1
ZONE 2
CAC-4
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
FIRE ALARM
SUPERVISORY
AC
NAC
ZONE
NAC
DISABLE
DISABLE
FAULT
POWER
ALARM
ACK
SILENCE
ENABLE/DISABLE
1
2
TB8
HOT NEUT EARTH
Nonpower-limited Circuits
C
NC NO
A-
A+
A-
A+
A-
ALARM
4XLB
CLASS A CLASS A
ZONE 3
ZONE 4
ZONE 1
TROUBLE
MAINTENANCE
ZONE 2
TROUBLE
MAINTENANCE
ZONE 3
TROUBLE
MAINTENANCE
ZONE 4
TROUBLE
MAINTENANCE
ALARM
SYSTEM
POWER
WALK
SILENCE
TROUBLE
TEST
TROUBLE
WALK
RESET
TEST
ZONE
3
4
JP1
JP2
EARTH BATT CHG
J8
BATTERY
SW1
SW2 SW3
Installation
C
NC NO
SUPV
Power-limited
Circuits
4XLM
4XTM
Nonpower-limited
Circuit
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-2404Notifier sfp-2402eNotifier sfp-2404e

Table of Contents