Connect Logic Control Inputs; Fig. 15: Pc2001-A1, Pc2002-A1, Pc2005-A1 And Pc2006-A1 Logic Control Input Connection; Table 7: Logic Control Inputs Connector - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

6.2.7 Connect logic control inputs

A6V10430579_en--_b
Digital audio matrices PC2001-A1, PC2002-A1, PC2005-A1 and PC2006-A1
The digital audio matrices provide one connector with 8 logic control inputs at the
rear of the housing.
The logic control inputs are used to get information and controls from the
connected components.
Logic 0 with input voltage < 3 V
Logic 1 with input voltage > 7 V
1
Logic Inputs

Fig. 15: PC2001-A1, PC2002-A1, PC2005-A1 and PC2006-A1 logic control input connection

Logic control inputs connector
Pin
Description
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
DI7
8
DI8
9
GND
10
10 V

Table 7: Logic control inputs connector

Use logic control inputs, see Use logic control inputs [➙ 69].
Install internal components
1
Logic Outputs
Remark
-
-
-
-
-
-
-
-
GND reference voltage
10 V reference voltage
6