6.23.8 Logic control outputs

A6V10430579_en--_b
The PCIO2001-A1 provides 16 logic control outputs on the 2 connectors 'X3' and
'X4'.
The logic control outputs are used to activate LEDs or communicate a status
change of the system.
The logic outputs are open collector outputs which switch to GND. A power supply
is required to use the outputs.
Logic control outputs connector - 'X3'
Pin
Description
1
O1
2
O2
3
O3
4
O4
5
O5
6
O6
7
O7
8
O8
9
GND
10
10 V

Table 79: PCIO2001-A1 logic control outputs connector - 'X3'

Logic control outputs connector - 'X4'
Pin
Description
1
O9
2
O10
3
O11
4
O12
5
O13
6
O14
7
O15
8
O16
9
GND
10
10 V

Table 80: PCIO2001-A1 logic control outputs connector - 'X4'

For use of logic control outputs, see Use logic control outputs [➙ 70].
Install internal components
Input/Output extension (digital 16) PCIO2001-A1
Remark
-
-
-
-
-
-
-
-
GND reference voltage
10 V reference voltage
Remark
-
-
-
-
-
-
-
-
GND reference voltage
10 V reference voltage