Connect Status Output Relays And Amplifier Activation; Fig. 60: Pv2003-A1 Status Output Relays And Amplifier Activation Connector; Table 40: Pv2003-A1 Status Output And Activation Connector - 'Control; Table 41: Pv2003-A1 Amplifier Activation With 'Auto On' Potentiometer - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

6
Install internal components
Power amplifier (4x150W) PV2003-A1

6.8.4 Connect status output relays and amplifier activation

Position
Turn to max left
In the middle
Turn to max right
82 | 173
The 'Power amplifier (4x150W)' PV2003-A1 provides one connect ('Control') to
report status of the amplifier and to activate the amplifier.
Link 1
Link 2

Fig. 60: PV2003-A1 status output relays and amplifier activation connector

Status output and activation connector - 'Control'
Pin
Description
1
CH A/B ok
2
CH A/B ok
3
CH C/D ok
4
CH C/D ok
5
DC 24 V ok
6
DC 24 V ok
7
AC 230 V ok
8
AC 230 V ok
9
CH A-D on +
10
CH A-D on -
11
Br. A-D on +
12
Br. A-D on -

Table 40: PV2003-A1 Status output and activation connector - 'Control'

The activation of the amplifiers is controlled by the 'Auto on' potentiometer.
Each amplifier actives by themselves when an analog audio signal is present at its
input. The threshold to activate the amplifier can be set with the potentiometer
between 7 mV to 300 mV.
Amplifier activation with 'Auto on' potentiometer
Description
Remark
Remote on
Activate with inputs of the 'control' connector pins 9-10 or 11-12
Auto on
Activates when signal is present
Always on
Amplifier is always active

Table 41: PV2003-A1 amplifier activation with 'Auto on' potentiometer

1
12
Remark
Relay output channel A/B ok, open: fault
Relay output channel A/B ok, open: fault
Relay output channel C/D ok, open: fault
Relay output channel C/D ok, open: fault
Relay output DC 24 V ok, open: fault
Relay output DC 24 V ok, open: fault
Relay output AC 230 V ok, open: fault
Relay output AC 230 V ok, open: fault
Activate channels A to D
Apply 12...24 V between pin 9 and 10
Activates channels A to D in the bridge mode
Apply 12...24 V between pin 11 and 12
A6V10430579_en--_b