Connect 'Pace-Net' Ethernet; Fig. 73: Pn2005-A1 Network Connectors - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

6
Install internal components
Planet IGS-10020MT Switch PN2005-A1

6.16.2 Connect 'PACE-Net' Ethernet

100 | 173
The switches are used to build a 'PACE-Net' communication network and to
connect 'PACE-Net' digital audio matrices, 'PACE-Net' call stations, Cerberus
PACE systems or a PC with the configuration tool 'PACE-Design' installed. The
Ethernet switch 'Planet IGS-10020MT Ethernet Switch' PN2005-A1 allows to build
a redundant Ethernet ring structure. It can also be used for tree and chain
structures.
9
10
7
8
5
6
3
4
1
2

Fig. 73: PN2005-A1 network connectors

The ports 1 to 8 are CAT5 copper Ethernet (RJ45, 10/100/1000Base-T) sockets.
The ports 9 and 10 are fiber optic slots for inserting SPF modules.
You can insert these SPF modules:
PNA2002-A1: 'Planet MGB-LX FOI Adapter', single mode, 10 km, 1310 nm
PNA2003-A1: 'Planet MGB-SX FOI Adapter', multi-mode, 550 m, 850 nm
PNA2004-A1: 'D-Link DEM-211 FOI Adapter', multi-mode, 2 km, 1310 nm
PNA2004-A1 is required to establish a fiber optic connection to 'Ethernet switch
(2x4/2)' PN2001-A1.