Logic Control Outputs; Table 100: Pt2001-A1 Logic Control Outputs Connector - 'Cn3 - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

7.1.8 Logic control outputs

A6V10430579_en--_b
The PT2001-A1 provides 4 logic outputs. They are open collector transistors
switching to GND.
The 4 logic control outputs can be used to switch lamps, relays or other
components with a current draw of max. 200 mA.
The output can be powered with the DC 10 V provided on pin 12 of the connector,
or with a voltage of max. DC 36 V.
Logic control outputs connector - 'CN3'
Pin
Description
1
Analog input 1
2
Analog input 2
3
Analog input 3
4
Analog input 4
5
Analog input 1
6
Analog input 2
7
Logic output 1
8
Logic output 2
9
Logic output 3
10
Logic output 4
11
GND
12
DC 10 V

Table 100: PT2001-A1 logic control outputs connector - 'CN3'

For more information, see Use logic control output [➙ 70].
Connect external components
Desk call station PT2001-A1
Remark
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
-
-
-
-
GND reference voltage
10 V reference voltage
7
129 | 173