7.14 Remote control panel PT2006-A1

7.14.1 Installation of PT2006-A1

A6V10430579_en--_b
The program channels of the connected digital audio matrix can be controlled with
the 'Remote control panel' PT2006-A1.
The PT2006-A1 is powered by DC 24 V and communicates via 'PACE-Bus'
(RS485) with the digital audio matrix.
Up to 8 PT2006-A1 can be connected to one digital audio matrix.
The PT2006-A1 can be mounted in the cabinet or outside of the cabinet. The
PT2006-A1 is designed to fit in a flush-mounted box.
If the PT2006-A1 is mounted outside of the cabinet, it is required to do the
following:
Secure the internal 24 V power supply voltage with a DC/DC converter
PCA2011-A1 or PCA2018-A1
Use an earth ground fault monitor PCA2001-A1 on the 24 V wiring
Isolate the internal 'PACE-Bus' (RS485) with the RS485 isolator PNA2009-A1
1
X1

Fig. 107: PT2006-A1 connector overview

The PT2006-A1 has one connector 'X1' to connect DC 24 V and 'PACE-Bus'
(RS485).
PT2006-A1 connector - 'X1'
Pin
Description
1
DC 24 V
2
DC 0 V
3
RX/D+
4
TX/D+
5
GND

Table 141: PT2006-A1 connector - 'X1'

Connect external components
Remote control panel PT2006-A1
Remark
-
-
RS485 data +
RS485 data -
GND reference voltage
7
167 | 173