4.20 Install logic control inputs

A6V11899867_en--_a
The PC1001-A3 and PC1002-A3 Cerberus PACE Compact digital audio matrix
boards both provide 1 connector ('DI') with 8 logic control inputs in the input/output
area.
The logic control inputs are used to get information and controls from the
connected devices.
Logic 0 with input voltage < 3 V
Logic 1 with input voltage > 7 V

Fig. 27: Logic control inputs

Logic control inputs connector - 'DI'
Pin
Description
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
DI7
8
DI8
9
GND
10
10 V

Table 24: Logic control inputs connector - 'DI'

Mounting/Installation
Install logic control inputs
Remark
-
-
-
-
-
-
-
-
GND reference voltage
10 V reference voltage
4
53 | 122