Table 125: Pto2009-A1 Ethernet In Connectors - 'Cn1' And 'Cn3; Table 126: Pto2009-A1 Ethernet Out Rj45 Connectors - 'J1' And 'J2; Table 127: Pto2009-A1 Fault Relay Connector - 'Cn6 - Siemens Cerberus PACE Manual

Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

Pin
Description
1
TX+
2
TX-
3
RX+
4
RX-
5
NC
6
Shield
Pin
Description
1
D1+/TX+
2
D1-/TX-
3
D2+/RX+
4
D3+
5
D3-
6
D2-/RX-
7
D4+
8
D4-
A6V10430579_en--_b
Ethernet in connectors - 'CN1' and 'CN3'
Remark: when used in a 2x4 wire cable
CAT5 pin
CAT5 according to T568B
1
White/orange
2
Orange
3
White/green
6
Green
-
Do not use
-
Shield

Table 125: PTO2009-A1 Ethernet in connectors - 'CN1' and 'CN3'

Ethernet out RJ45 connectors - 'J1' and 'J2'
Remark: when used in a 2x4 wire cable
CAT5 pin
CAT5 according to T568B
1
White/orange
2
Orange
3
White/green
6
Blue
-
White/blue
-
Green
-
White/brown
-
Brown

Table 126: PTO2009-A1 Ethernet out RJ45 connectors - 'J1' and 'J2'

Fault relay connector - 'CN6'
Pin
Description
1
DC 10 V
2
A-24 V
3
B-24 V

Table 127: PTO2009-A1 fault relay connector - 'CN6'

Connect external components
Call station interface (redundant) PTO2009
Fire alarm cables color code
according to VDE0815
Grey
Yellow
Brown
Green
Do not use
Shield
Fire alarm cables color code
according to VDE0815
Grey
Yellow
Brown
Red
Blue
Green
White
Black
Remark
10 V reference voltage
Connected to 10 V if 'Power In A', 'CN2' has
a fault
Connected to 10 V if 'Power In B', 'CN4' has
a fault
7
159 | 173