Connect Dc 24 V Power Supply; Connect 'Pace-Bus' (Rs485); Logic Control Outputs; Table 35: Pt1001-A1 Dc 24 V Power Supply Connector - 'X1 - Siemens Novigo Core Installation, Mounting

Table of Contents

Advertisement

6
Install internal components
System operating unit PT1001-A1

6.1.4 Connect DC 24 V power supply

6.1.5 Connect 'PACE-Bus' (RS485)

6.1.6 Logic control outputs

68 | 121
The PT1001-A1 provides one DC 24 V power supply connector ('X1').
DC 24 V power supply connector - 'X1'
Pin
Description
1
DC 24 V
2
DC 0 V

Table 35: PT1001-A1 DC 24 V power supply connector - 'X1'

The PT1001-A1 provides one 'PACE-Bus' (RS485) connector ('X2').
'PACE-Bus' (RS485) connector - 'X2'
Pin
Description
1
D-
2
D+
3
GND

Table 36: PT1001-A1 'PACE-Bus' (RS485) connector - 'X2'

The PT1001-A1 provides 4 logic control outputs on the connector 'X3'.
The logic control outputs are used to activate LEDs or communicate a status
change of the system.
The logic control outputs are open collector outputs which switch to IO-GND. A
power source is required to use the outputs.
Max. current per output is 200 mA.
Max. current on internal 12 V power source is 250 mA.
Logic control outputs connector - 'X3'
Pin
Description
1
O1
2
O2
3
O3
4
O4
5
IO-GND
6
12 V

Table 37: PT1001-A1 logic control outputs connector - 'X3'

For use of logic control outputs, see Use logic control output [➙ 82].
Remark
-
-
Remark
RS485 data -
RS485 data +
GND reference voltage
Remark
-
-
-
-
IO-GND not connected to GND
12 V reference voltage
A6V11940317_en--_a