Wiring the channels
April 2022
4.6
Wire the discrete output
Use this section to wire the discrete output in explosion-proof, nonincendive, or
nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
4.6.1
Wire the discrete output (internally powered)
Use this procedure to wire the internally-powered discrete output for Channel B or C.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-16: Discrete output wiring (internally powered)
A
A. Discrete output
B. Channel B or C
C. See
D. Counter
Figure 4-17: Internally powered discrete output: output amplitude versus load
resistance [24 VDC (Nom) open circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
34
B
Figure 4-17
for output amplitude versus load resistance
24
22
20
18
16
14
A
12
10
8
6
4
2
0
0
Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
750
1500
2250
B
Installation Manual
MMI-20027478
C
D
3000