Special Notes Regarding Ul Hazardous Location - WAGO 750 XTR Manual

Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

54
Use in Hazardous Environments
7.2.2

Special Notes Regarding UL Hazardous Location

For UL Hazardous Location acc. to UL File E198726, the following additional
requirements apply:
Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only
ETHERNET connections are used exclusively for connecting to computer
networks (LANs) and may not be connected to telephone networks or
telecommunication cables
WARNING – The radio receiver module 750-642 may only be used to
connect to external antenna 758-910!
WARNING – Product components with fuses must not be fitted into circuits
subject to overloads!
These include, e.g., motor circuits.
WARNING – When installing I/O module 750-538, "Control Drawing No.
750538" in the manual must be strictly observed!
Additional Information
Proof of certification is available on request.
Also take note of the information given on the operating and assembly
instructions.
The manual, containing these special conditions for safe use, must be readily
available to the user.
Manual
Version 1.0.0
750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR
WAGO I/O System 750 XTR