Table2.1 Restrictions on system configuration, available base units, extension cables, and power supply modules
CPU number
Maximum number of
extension stages
Maximum number of
mountable I/O
modules
Available main base
unit model
Model not requiring power supply module
Available extension
Model requiring Q series power supply
base unit model
module
Available extension
cable model
Available power
supply module model
CPU1: CPU No. 1 (Basic model QCPU), CPU2: CPU No. 2 (Motion CPU),
CPU3: CPU No.3 (PC CPU module/C Controller module)
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P, Q64PN
Precautions
• Do not use an extension cable longer than 13.2m (43.31 ft).
• When using an extension cable, keep it away from the main circuit (high voltage
and large current) line.
• Set the number of extension stages so as not to be duplicated.
• The QA1S6 B, QA6 B, QA6ADP+A5 B/A6 B, or Q6R B cannot be
connected as an extension base unit.
• Although there is no restriction on the connection order of the Q5 B and the
Q6 B, check the availability of them by referring to QCPU User's Manual
(Hardware Design, Maintenance and Inspection) when both the Q5 B and the
Q6 B exist as the extension base unit.
• Connect the OUT connector of an extension base unit and the IN connector of
the adjacent extension base unit by an extension cable.
• When 26 modules or more are mounted, an error "SP. UNIT LAY ERR." (error
code: 2124) occurs. (The number of mountable modules includes one CPU
module.)
• The redundant base unit cannot be used when the Basic model QCPU is
mounted on the multiple CPU system.
• "No. of CPUs" is the number of CPUs set by [No. of PLC] of GX Developer.
• The PC CPU module occupies two slots. Therefore, when the PC CPU module is
used, the maximum number of I/O modules is decreased by 1 from the value
indicated in Table 2.1.
• The PC CPU module and C Controller module cannot be mounted together:
therefore; mount either of them.
• For details of the Motion CPU, PC CPU module, and C Controller module, refer to
the manuals of each CPU module.
2.1.1 System configuration using Basic model QCPU (Q00CPU, Q01CPU)